Etats-Unis : Prairie Island : Indisponibilité des lignes d’alimentation électrique d’urgence par les diesels de secours




3 juin 2014


Indisponibilité des deux diesels d’alimentation d’urgence du réacteur n° 1. Malgré cette défaillance, le réacteur a été maintenu à pleine puissance. Un contournement du défaut a été obtenu 1h après sa découverte pour un diesel et 1h54 pour le second diesel.

Type : PWR - Puissance : 1 677 MWth - Première divergence : 12/1973

Available in english only.


Number : 50170

Facility : PRAIRIE ISLAND - State : MN - Unit : [1] - RX Type : [1]

Event Date : 06/03/2014 - Event Time : 19:02

Emergency Class : NON EMERGENCY 10 CFR Section : 50.72(b)(3)(v)(D) - ACCIDENT MITIGATION

Initial PWR : 100 % Current PWR : 100 %

Event Text

DIESEL GENERATORS DECLARED INOPERABLE DUE TO NOT MEETING HIGH ENERGY LINE BREAK REQUIREMENTS

"D1 and D2 Emergency Diesel Generators (DG) were declared inoperable at 1902 CDT due to the station identifying that the Turbine Building HELB [High Energy Line Break] heatup analysis temperature of 270 F exceeded the maximum temperature limit of 200 F for both diesel generators supply and exhaust fan blade positioners.

"LCO 3.8.1 Condition B was entered for both DGs and LCO 3.8.1 Condition E was entered for two DGs inoperable on the same unit. The DGs could start and run if required at the time of entry.

"This condition is reportable per 10 CFR 50.72(b)(3)(v) as an event or condition that could have prevented the fulfillment of a safety function.

"Unit 1 continued to operate in Mode 1 at 100% power while bypasses were being put in-service to fail the diesel generators supply and exhaust fan blade positioners in the full cooling mode to allow the LCO conditions to be exited.

"At 2002 CDT the bypasses were installed on the D1 Diesel Generator Supply and Exhaust Fan Blade Positioners therefore LCO 3.8.1 Condition E was exited for both D1 and D2 Emergency Diesel Generators being inoperable. In addition LCO 3.8.1 Condition B was exited for D1 Diesel Generator due to it being declared Operable.

"At 2056 CDT the bypasses were installed on the D2 Diesel Generator Supply and Exhaust Fan Blade Positioners therefore LCO 3.8.1 Condition B was exited for D2 Diesel Generator due to it being declared Operable.

"At no time was the health and safety of the public threatened.

"The Senior NRC Resident has been notified."

https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2014/20140604en.html

>>