Etats-Unis : Comanche Peak : L’hypothèse d’un type d’incendie a montré son impact sur des éléments important de mise à l’arrêt sûr du réacteur




8 octobre 2013


Des prescriptions n’ont pas été respectées concernant les protections d’ampèremètre qui pourraient être à l’origine d’un départ d’incendie. Ce problème pourrait compromettre le système de mise en arrêt sûr des deux réacteurs du site.

Type : BWR - P. : n°1 = 3 612 MWth - n°2 = 3 458 MWth - Première divergence : n°1 : 4 1990 - n°2 : 3 1993

Available in english only.


Event Number : 49419 Facility : COMANCHE PEAK - State : TX - Unit : [1] [2] - RX Type : [1] W-4-LP,[2] W-4-LP

Event Date : 10/08/2013 - Event Time : 12:40 - Emergency Class : NON EMERGENCY 10 CFR Section : 50.72(b)(3)(ii)(B) - UNANALYZED CONDITION

Initial PWR : 100 % Current PWR : 100 %

Event Text

POSTULATED HOT SHORT FIRE EVENT THAT COULD ADVERSELY IMPACT SAFE SHUTDOWN EQUIPMENT

"A review of industry operating experience regarding the impact of unfused Direct Current (DC) ammeter circuits in the control room has determined the described condition to be applicable to Comanche Peak Nuclear Power Plant resulting in a potentially unanalyzed condition with respect to 10CFR50 Appendix R analysis requirements. The original plant wiring design and associated analysis for the Class 1 E batteries control room ampere indications do not include overcurrent protection features to limit the fault current.

"In the postulated event, a fire in the control room could cause one of the ammeter wires to hot short to the ground plane. Simultaneously, the fire causes another DC wire from the opposite polarity on the same battery to also hot short to the ground plane. This could cause a ground loop through the unprotected ammeter wiring. This event could result in excessive current flow (heating) in the ammeter wiring to the point of causing a secondary fire in the raceway system. The secondary fire could adversely affect safe shutdown equipment and potentially cause the loss of the ability to conduct a safe shutdown as required by 10CFR50 Appendix R.

"This condition is reportable in accordance with 10CFR50.72(b)(3)(ii)(B) as an unanalyzed condition. Compensatory measures (fire watches) have been implemented for affected areas of the plant."

The licensee has notified the NRC Resident Inspector.

See related Event #49411.

Source : https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2013/20131009en.html


La surveillance des installations nucléaires au quotidien ? C’est grâce à vos dons que nous pouvons la mener !
Pour surveiller au jour le jour les incidents dans les installations nucléaires, les décrypter et dénoncer les risques permanents qui sont trop souvent minimisés - voire cachés par les exploitants, nous mobilisons tout au long de l’année des moyens humains et techniques.
Pour continuer ce travail de lanceur d’alerte et donner, au plus proche de leur survenue, des informations sur les inquiétants dysfonctionnements d’un parc nucléaire vieillissant, nous avons besoin de votre soutien financier !

Faire un don