Etats-Unis : Duane Arnold : Démarrage intempestif des diesels de secours suite à une perturbation électrique




30 juin 2014


Suite à cette baisse de tension due à un orage, les deux groupes électrogènes ont démarré automatiquement, mais n’ont pas pris le relais de l’alimentation électrique du réacteur. La centrale a continué d’être alimentée normalement par les lignes extérieures.

Type : Fukushima 1 (BWR Mark I) - Puissance : 1 912 MWth - Première divergence : 03/1974 (soit 40 ans)

Available in english only.


Event Number : 50246

Facility : DUANE ARNOLD

State : IA - Unit : [1] - RX Type : [1] GE-4 -

Event Date : 06/30/2014 - Event Time : 19:13 [CDT]

Emergency Class : NON EMERGENCY 10 CFR Section : 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION

Unit SCRAM Code RX CRIT Initial PWR Initial RX Mode Current PWR Current RX Mode 1 N Y 98 Power Operation 98 Power Operation

Event Text :

AUTO-START OF STANDBY DIESEL GENERATORS DUE TO A GRID DISTURBANCE

"This report is being made under 10CFR50.72(b)(3)(iv)(A), ’Any event or condition that results in valid actuation of any of the systems listed in paragraph (b)(3)(iv)(B) of this section’ due to an auto start of ’A’ and ’B’ Standby Diesel Generators. At 1913 CDT, a grid disturbance during a local thunderstorm caused a valid bus undervoltage condition that resulted in the auto start of both the ’A’ and ’B’ Standby Diesel Generators. The ’A’ and ’B’ Standby Diesel Generator supply breakers did not close onto their respective buses as they remained powered by their normal power supply, the 1X003 Startup Transformer, during and after the event. NextEra Duane Arnold personnel inspections revealed no issues with breakers in the switchyard. Ltc (Iowa Transmission Company) reported a fault on a 161 Kv line in the NextEra Duane Arnold vicinity. Offsite power remained Operable during and following the event.

"As designed the ’A’ and ’B’ Emergency Service Water systems auto started when the diesel generators auto started. The Emergency Service Water systems and both Standby Diesel Generators have been returned to standby/readiness condition. All ECCS [Emergency Core Cooling System] systems were available before the event and have remained available following the event."

The licensee notified the NRC Resident Inspector.

https://www.nrc.gov/reading-rm/doc-collections/event-status/event/2014/20140701en.html#en50246